What this subject covers

Measuring temperature, pressure, flow, force and moisture, logging the data, and controlling processes automatically.

In the exams: ICAR AICE subjects 38 (Unit 7), 39 (Unit 8) and 41 (Unit 9); NCEES PE sensors and data acquisition; NCEES FE 4–6 questions

What NCEES FE Other Disciplines asks from it

NCEES FE Other Disciplines — Instrumentation and Controls (4–6 questions)

Sensors and transducers, bridge circuits, sampling and ADC resolution, block diagrams, closed-loop transfer functions, steady-state error, stability and first- and second-order response.

Where the 35 questions fall

How our questions for NCEES FE Other Disciplines spread across the units of Instrumentation, Sensors & Process Control. Difficulty: 6 easy, 24 medium, 5 hard.

Control modes: on-off, P, PI and PID8
Signal conditioning6
Pressure, flow and level measurement5
Static and dynamic characteristics of instruments4
The generalised measurement system3
Temperature transducers3
Data acquisition and data loggers3
Force, torque and strain: strain gauges and load cells2
Programmable logic controllers1

6 practice questions, worked

Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.

1 · Static and dynamic characteristics of instruments · medium

A thermometer with a first-order time constant of 10 s is moved from air at 20 °C into hot water at 80 °C. What does it read 15 s later?

  1. 57.9 °C
  2. 62.1 °C
  3. 33.4 °C
  4. 66.6 °C
Answer and working

D. 66.6 °C

y = 80 − (80 − 20)e^(−15/10) = 80 − 60 × 0.2231 = 66.6 °C. 57.9 °C is the reading at one time constant (10 s), 62.1 °C ignores the 20 °C starting point, and 33.4 °C adds the remaining fraction instead of the completed fraction.

2 · Static and dynamic characteristics of instruments · medium

Dryer plenum air warms steadily at 2 °C per minute. The air-temperature sensor is first-order with a time constant of 30 s. Once the ramp is established, how far does the reading lag behind the true temperature?

  1. 60 °C
  2. 1.0 °C
  3. 2.0 °C
  4. 0.033 °C
Answer and working

B. 1.0 °C

For a ramp, a first-order sensor lags by rate × τ = (2 °C/60 s) × 30 s = 1.0 °C. 60 °C multiplies 2 by 30 without converting minutes to seconds; 2.0 °C would correspond to a 60 s time constant; 0.033 °C is the rate per second, not the lag.

3 · Temperature transducers · medium

A Pt100 sensor (α = 0.00385 /°C, linear model) in a pasteuriser hot-water line reads 119.4 Ω. What is the temperature?

  1. 310.1 °C
  2. 19.4 °C
  3. 50.4 °C
  4. 7.5 °C
Answer and working

C. 50.4 °C

R = R0(1 + αT), so T = (R/R0 − 1)/α = (1.194 − 1)/0.00385 = 50.4 °C. 310.1 °C forgets to subtract 1; 19.4 °C takes the ohms change as degrees; 7.5 °C multiplies the 19.4 Ω change by α (with a factor-of-100 slip) instead of dividing.

4 · Pressure, flow and level measurement · medium

An orifice meter gives 16 kPa differential at 40 L/s. If flow falls to 20 L/s, what differential will it show?

  1. 8 kPa
  2. 2 kPa
  3. 4 kPa
  4. 32 kPa
Answer and working

C. 4 kPa

Q ∝ √Δp, so Δp ∝ Q². Halving flow divides Δp by four: 16/4 = 4 kPa. 8 kPa assumes a linear relation, which is why obstruction meters have limited turndown. 2 kPa assumes Δp ∝ Q³; 32 kPa doubles instead of quartering.

5 · Data acquisition and data loggers · easy

What is the size of one least significant bit (LSB) for a 12-bit ADC with a 0–5 V input range?

  1. 4.88 mV
  2. 417 mV
  3. 1.22 mV
  4. 2.44 mV
Answer and working

C. 1.22 mV

LSB = FS/2ⁿ = 5/4096 = 1.22 mV. 4.88 mV is the 10-bit value; 417 mV divides by the number of bits instead of 2ⁿ; 2.44 mV assumes a 10 V range.

6 · Control modes: on-off, P, PI and PID · medium

In an ultimate-cycle test on a dryer burner loop, sustained oscillation occurs at Ku = 8 with period Pu = 120 s. What are the Ziegler–Nichols PID settings?

  1. Kp = 3.6, Ti = 100 s, Td = 15 s
  2. Kp = 4.0, Ti = 60 s, Td = 30 s
  3. Kp = 4.8, Ti = 120 s, Td = 60 s
  4. Kp = 4.8, Ti = 60 s, Td = 15 s
Answer and working

D. Kp = 4.8, Ti = 60 s, Td = 15 s

Ziegler–Nichols PID: Kp = 0.6Ku = 4.8, Ti = Pu/2 = 60 s, Td = Pu/8 = 15 s. Kp = 3.6 with Ti = 100 s is the PI rule; 0.5Ku is the P-only rule. These settings give quarter-amplitude decay and are usually softened in practice.

Ten here, 35 in the app. The Laisha app has every practice question we have written to NCEES FE Other Disciplines in this subject, marked as you go, with timed papers, a jump-to-unanswered list and a certificate when you pass at 70 per cent.

Free for ten days, then one subscription of US$10 a month. We would rather say so here than have you find it later.

Practise the full set in Laisha →

Read the subject

Instrumentation, Sensors & Process ControlThe full study manual, free NCEES FE Other DisciplinesFormat, sections and how it has changed

More NCEES FE Other Disciplines practice

Engineering ThermodynamicsEngineering Physics & ChemistryEngineering Mechanics (Statics & Dynamics)Strength of MaterialsProbability, Statistics & Data AnalysisEngineering MathematicsFluid Mechanics & Open Channel HydraulicsEngineering Economics, Project & Business ManagementHeat & Mass TransferProfessional Practice, Ethics & LawsBasic Electrical & Electronics EngineeringMachine Design

Instrumentation, Sensors & Process Control for other exams

ICAR AICE-JRF/SRF · IndiaNCEES PE Agricultural and Biological Engineering · USAICAR AIEEA-PG · India

Ask Laisha about this

Opens Laisha's chat with your question ready to send. Sign in or start free.