Original practice questions written to the published syllabus · not past papersAgricultural and Biosystems Engineers Licensure Examination (ABELE) is a licensing and registration exam run by Professional Regulatory Board of Agricultural and Biosystems Engineering, PRC, for candidates in Philippines. Paper-based, 2 days (Day 1 6 hours; Day 2 5 hours + 4 hours). Non-programmable calculator only; the Dec 2025 programme bans the Casio fx-991ES/ES Plus by name.
Source: prc.gov.ph.
Checked against the exam body's published information. Formats and fees change; confirm the current edition there before you book.
Refrigeration cycles, equipment and cold-store design, from COP to the heat load of a room full of potatoes.
Our 17 Agricultural and Biosystems Engineers Licensure Examination questions in this subject: 0 easy, 12 medium, 5 hard, across 10 units.
Choose an answer, then open the working. Each explanation says why the right answer is right and why the others are not.
These 10 were written to Agricultural and Biosystems Engineers Licensure Examination and are not shown on any other exam's page.
A single-effect absorption chiller delivers 100 kW of cooling with a COP of 0.7. Neglecting pump work, the heat that the cooling tower must remove from absorber and condenser is about
A. 243 kW
Generator heat Q_G = 100/0.7 = 142.9 kW. Heat rejected = Q_E + Q_G = 100 + 142.9 = 242.9 kW. 143 kW is only the driving heat; 125 kW is what a compression chiller of COP 4 would reject, which is why absorption plants need larger cooling towers.
A designer wants 90–95% relative humidity in a room storing leafy vegetables. The evaporator should be selected with
B. A small air-to-refrigerant temperature difference, and therefore a large coil surface
A large TD cools air far below its dew point and strips moisture, drying the room and the produce. A small TD (often a few kelvin) keeps humidity high at the cost of a larger coil. A low evaporating temperature also lowers COP.
A technician finds a thermostatic expansion valve whose sensing bulb has lost its charge. The system will most likely show
C. A starved evaporator with high superheat and low suction pressure, as the valve closes
Bulb pressure is the opening force; without it, evaporator pressure and spring close the valve. The evaporator is starved, suction pressure falls and superheat is high. Flooding would follow if the bulb were detached and warm, or the valve stuck open.
2 m³/s of air (density 1.2 kg/m³, humid specific heat 1.02 kJ/kg K) is cooled sensibly from 30 °C to 18 °C. The sensible cooling load is about
A. 29.4 kW
Q = V ρ c_p Δt = 2 × 1.2 × 1.02 × 12 = 29.4 kW (≈ 8.4 TR). Using volume without density gives 24.5; using water's c_p gives 120.6.
A freezer wall must limit heat flux to 8 W/m² with a 40 K temperature difference. Neglecting surface resistances, the thickness of insulation with k = 0.024 W/m K required is
D. 120 mm
q = kΔT/x → x = kΔT/q = 0.024 × 40/8 = 0.120 m = 120 mm. 12 mm is a metre-to-millimetre slip; 4.8 mm comes from the wrong rearrangement qk/ΔT, and 208 mm from ΔT/(qk) with the units mislabelled.
A store holds 500 t of a vegetable whose tabulated heat of respiration at the storage temperature is taken as 20 mW/kg. The respiration load is
B. 10 kW
Q = 500,000 kg × 0.02 W/kg = 10,000 W = 10 kW. Treating watts as kilowatts gives 10,000; multiplying by 24 turns a rate into a daily energy in the wrong unit. The figure is illustrative: respiration heat varies strongly with commodity, cultivar and temperature. 0.01 kW treats the 500 t as 500 kg (500 × 0.02 W).
A cold store's calculated 24-hour load is 2,000 MJ. With a 10% safety factor and the plant planned to run 20 h a day, the refrigeration capacity to specify is about
C. 30.6 kW (8.69 TR)
Capacity = 2,000,000 kJ × 1.10/(20 × 3,600 s) = 30.6 kW = 8.69 TR. Dividing by 24 h (25.5 kW) leaves no time for defrost or reserve; omitting the safety factor gives 27.8 kW. 1833 kW divides by minutes instead of seconds (2,200,000/1,200).
Four workers, each taken as releasing 300 W in a freezer, work inside for 8 h a day. The daily occupancy load is
C. 34,560 kJ
E = 4 × 300 W × 8 h × 3,600 s/h = 34,560,000 J = 34,560 kJ (9.6 kWh). 9,600 is watt-hours written as kJ; 24 h assumes the workers never leave. 103,680 kJ assumes 24 h of occupancy, and 576.0 kJ uses minutes instead of seconds (4 × 0.3 kW × 8 × 60).
Under the UN ATP Agreement, a 'heavily insulated' (IR) body for carriage of perishable foods must have an overall heat-transfer coefficient K of not more than
C. 0.40 W/m² K
ATP defines normal insulated equipment (IN) as K ≤ 0.70 W/m² K and heavily insulated (IR) as K ≤ 0.40 W/m² K.
A reefer body has K = 0.4 W/m² K and mean surface area 80 m². Frozen cargo is carried at −18 °C with an ambient of 27 °C. The steady heat leak through the body is
A. 1440 W
Q = K A ΔT = 0.4 × 80 × 45 = 1440 W. ΔT is 27 − (−18) = 45 K; using 27 − 18 = 9 K is a sign slip. The refrigeration unit must exceed this with margin for door openings and ageing of insulation. 1.44 W is a kW-to-W slip, and 288 W uses the 9 K sign slip (0.4 × 80 × 9).
This plan follows where our questions actually fall, so the time goes where the marks are likely to be. It is our reading of the syllabus, not the exam body's weighting.
Read the manual chapters for these first and do every worked question you can find on them.
Aim for one sitting per unit, then mixed questions across them.
Learn the definitions, classifications and standard numbers; these units are more often recalled than worked.
Come back to these after a first pass, untimed, and read every explanation, including for the options you rejected.
Last updated · How Laisha writes and checks its pages · Report a mistake
US$10 a month · one price worldwide · cancel any time
| Free | Smarter | |
|---|---|---|
| Grow guides, pest pages, articles | Read all | Read all |
| Ask Laisha | 5 a day | Up to 1,000 a month |
| Exam practice | The sample on each page | Every question, timed papers |
| Crop calendar and pest alerts | — | For your own fields |
| Calculators and tools | — | All |
| Uploads and reports | — | 100 a month, real files |
An AI operating system for agriculture: free guides, manuals and tools written for every country.